Types:

3 bar | 70° C | F 8 – F 24

 

Technical Features:

  • Shallow form vessel for closed heating and cooling systems, designed, in particular, for installation in the boiler
  • With thread connections
  • From 18 litres, with bracket
  • Non-replaceable diaphragm to DIN EN 13831
  • Permissible operating temperature 70°C
  • For antifreeze addition of at least 25–50 %
  • Approval according to Pressure Equipment Directive 97/23/EC
  • Long-lasting epoxy resin coating
  • With factory-pressurised gas chamber
  • Max. permissible system temperature 120°C

Reflex C

 

Types:

3 bar | 70° C | C 8 – C 80

 

Technical Features:

  • For closed heating and cooling systems
  • With thread connections
  • Including brackets for easy installation
  • Non-replaceable bladder to DIN EN 13831
  • Permissible operating temperature 70°C
  • For antifreeze addition of at least 25–50%
  • Approval according to Pressure Equipment Directive 97/23/EC
  • Long-lasting epoxy resin coating
  • With factory-pressurised gas chamber
  • Max. permissible system temperature 120°C

Reflex N

 

Types:

3 bar | 70° C | N 8 – N 35

6 bar | 70° C | N 50 – N 1000

 

Technical Features:

  • For closed heating and cooling systems
  • With thread connections
  • Vertical from 35 litres
  • Non-replaceable diaphragm to DIN EN 13831
  • Max. operating temperature 70°C
  • For antifreeze addition of at least 25–50%
  • Approval according to Pressure Equipment Directive 97/23/EC
  • Long-lasting epoxy resin coating
  • With factory-pressurised gas chamber
  • Max. permissible system temperature 120°C

Reflex S

 

Types:

10 bar | 70° C | S 2 – S 600

 

Technical Features:

  • For solar, heating and cooling systems
  • With thread connections
  • Up to 33 litres with brackets, from 50 litres with adjustable feet
  • For antifreeze addition of at least 25–50%
  • Up to 33 litres non-replaceable bladder, non-replaceable diaphragm for 50–600 litres
  • Max. operating temperature 70°C
  • Approval according to Pressure Equipment Directive 97/23/EC
  • Long-lasting epoxy resin coating
  • With factory-pressurised gas chamber
  • Max. permissible system temperature 120°C

Reflex G

 

Types:

6 bar | 70° C | G 100 – G 5000

10 bar | 70° C | G 100 – G 5000

16 bar | 70° C | G 100 – G 5000

 

Technical Features:

  • For closed heating and cooling systems
  • Vertical design
  • Connections:
    Up to 1,000 litres/Ø 740 mm with thread connection
    From 1,000 litres / Ø 1,000 mm with DN65 flange connections
  • Replaceable bladder to DIN EN 13831
  • Max. operating temperature 70°C
  • For antifreeze addition of at least 25–50 %
  • Approval according to Pressure Equipment Directive 97/23/EC
  • From 1,000 litres, with bladder rupture detector
  • With viewing opening (from 1,000 litres with 1,000 mm Ø)
  • Pressure gauge and supply pressure valve protected by clip
  • Long-lasting epoxy resin coating
  • With factory-pressurised gas chamber
  • Max. permissible system temperature 120°C

Reflex V

 

Types:

6 bar | 120° C | V 500 – V 5000

10 bar | 120° C | V 6 – V 5000

 

Technical Features:

  • Auxiliary vessels
  • Up to 20 litres with brackets, from 40 litres with adjustable feet
  • Without membrane
  • Required in systems with return temperatures > 70°C or cooling systems with temperatures < 0°C
  • Approval according to Pressure Equipment Directive 97/23/EC
  • Can also be used as a buffer tank
  • Special vessel > 10bar/ > 120°C available upon request
  • Long-lasting epoxy resin coating
  • Max. permissible system temperature 120°C

Refix

Refix DD

 

Types:

10 bar | 70° C | DD 2 – DD 33

25 bar | 70° C | DD 8 – DD 8

 

Technical Features:

  • For potable water, pressurerising and water-heating systems according to DIN 1988
  • With stainless thread connection
  • 33 litres with brackets
  • Flow-through with high-flow circulation star
  • Non-replaceable bladder to DIN EN 13831, DIN 4807 T5, KTW-C and W270
  • Built and tested to DIN 4807 T5, DIN DVGW Reg. No. NW-0411AT2534
  • Approval according to Pressure Equipment Directive 97/23/EC
  • Interior and exterior coating in compliance with KTW-A
  • May be combined with the Flowjet—flow through valve
  • Long-lasting epoxy resin coating
  • With factory-pressurised gas chamber
  • Vessels certified to WRAS and ACS upon request

Refix DT

 

Types:

10 bar | 70° C | DT 60 – DT 3000

16 bar | 70° C | DT 80 – DT 3000

 

Technical Features:

  • For potable water, pressurerising and water-heating systems according to DIN 1988
  • Flowjet incl. isolation and drainage or dual connection
  • Replaceable bladder to DIN EN 13831, DIN 4807 T5, KTW-C and W270, built and tested to DIN 4807 T5, DIN DVGW Reg. No. NW-0411AT2534
  • Approval according to Pressure Equipment Directive 97/23/EC
  • Interior and exterior coating in compliance with KTW-A
  • From 1,000 litres, with bladder rupture detector
  • Pressure gauge and supply pressure valve protected by clip
  • Long-lasting epoxy resin coating
  • With factory-pressurised gas chamber
  • Vessels certified to ACS upon request

Refix C-DE

 

Types:

10 bar | 70° C | C-DE 8 – C-DE 80

 

Technical Features:

  • Vertical, discus-shaped shallow vessels for heating, heat pump, cooling and solar applications as well as service water applications not required to meet the DIN 1988 requirements
  • With stainless thread connection
  • Non-replaceable bladder to DIN EN 13831
  • No flow through, no isolation
  • Components in contact with water are corrosion-protected
  • Approval according to Pressure Equipment Directive 97/23/EC
  • For antifreeze addition of at least 25–50%
  • Long-lasting epoxy resin coating
  • With factory-pressurised gas chamber

Refix DE

 

Types:

10 bar | 70° C | DE 2 – DE 5000

16 bar | 70° C | DE 8 – DE 5000

25 bar | 70° C | DE 8 – DE 3000

 

Technical Features:

  • Only for systems not required to meet DIN 1988, such as fire-fighting and service water systems, underfloor heating and geothermal installations
  • 33 litres with brackets
  • Components in contact with water are corrosion-protected
  • Bladder to DIN EN 13831 / replaceable from 50 litres
  • No flow through, without isolation, without drain
  • From Ø 1,000 mm including pressure gauge
  • Pressure gauge and supply pressure valve protected by clip
  • Approval according to Pressure Equipment Directive 97/23/EC
  • Long-lasting epoxy resin coating
  • With factory-pressurised gas chamber
  • Vessels certified to WRAS and ACS upon request

Refix HW

 

Types:

10 bar | 70° C | HW 25 – HW 100

 

Technical Features:

  • As a buffer vessel for domestic water systems not subject to the DIN 1988 requirements
  • Container surface and water-touching parts are corrosion-protected
  • Bladder to DIN EN 13831 / replaceable from 50 litres
  • Max. operating temperature 70°C
  • Approval according to Pressure Equipment Directive 97/23/EC
  • Long-lasting epoxy resin coating
  • With factory-pressurised gas chamber
  • Vessels certi ed to WRAS and ACS upon request

Refix DC

 

Types:

10 bar | 70° C | DC 25 – DC 600

 

Technical Features:

  • Only for systems not required to meet DIN 1988, such as fire-fighting and service water systems, under floor heating
  • Components in contact with water are corrosion-protected
  • Non-replaceable diaphragm to DIN EN 13831
  • No flow through, without isolation, without drain
  • Approval according to Pressure Equipment Directive 97/23/EC
  • Long-lasting epoxy resin coating
  • With factory-pressurised gas chamber
  • Vessels certi ed to WRAS and ACS upon request